HomeProductsMechanical Shock Tester
Fire Mechanical Shock Tester, CFMT 2008, IEC 60331-12 & 31
FESTEC¡¯s IEC 60331-12 tester is used in test conditions where the basic flame temperature is at least 830¡É and tests the cable exposed to flame and mechanical shock that needs to maintain the circuit integrity.

   
• IEC 60331
  - Test for electric cables under fir conditions – Circuit integrity
• IEC 60331 Part 12
  - Apparatus – Fire with shock at a flame temperature of at least 830¢ªC
• IEC 60331 Part 31
  - Procedures and requirements for fire with shock – Cables of rated voltage up to and including 0.6/1kV
• IEC 60331-1
  - Test method for fire with shock at a temperature of at least 830 ¡ÆC for cables of rated voltage up to and including 0,6/1,0 kV and with an overall diameter exceeding 20 mm
• IEC 60331-2
  - Test method for fire with shock at a temperature of at least 830 ¡ÆC for cables of rated voltage up to and including 0,6/1,0 kV and with an overall diameter not exceeding 20 mm
• IEC 60331-3
Test method for fire with shock at a temperature of at least 830 ¡ÆC for cables of rated voltage up to and including
  - 0,6/1,0 kV tested in a metal enclosure
- Test Chamber Size : (W) 2,500 x (D) 1,800 x (H) 1,600 mm
- Test Apparatus(Test Ladder) Size : (L) 1,200  x (H)  600  mm
- AC Motor : 4 pole / 3 P / 220VAC / 60 Hz / 1,550 RPM / 9.40 kg-cm
- Heat Source : Ribbon type Propane Gas Burner
- Burner Dimension : (L) 500 x (W) 10 mm / Space of hole : 3.2mm
- Auto Ignition system
- Mass Flow Controller
; Gas : 15 SLPM / Signal Output : 0 ~ 5V / Accuracy : ¡¾1 % fo F.S
; Air  : 180 SLPM / Signal Output : 0 ~ 5V / Accuracy : ¡¾1 % fo F.S
- Electric Control : Transformer & Slidacs : 3 Phase 3 wire, 100~1,000V
- DAQ System
; 16 channel Analog Input / Output, 200ks/s
; 16 channel Digital Input / Output
Control Rack : (W) 730 x (D) 650 x (H) 1,400 / 19¡± Rack / Each Assembly Connector
Specification
Size 1,600(W)¡¿850(D)¡¿1,900(H)mm
Power AC 380V 3-phase, 50/60Hz, 30A
Weight 100 kg
Manual Supply
Exhaust Minimum 15§©/min
Utilities Propane Gas, Compressed Air, Personal Computer, Dust Collector
• The burner has a Ventury Mixer structure and it¡¯s a ribbon type propane gas burner with front length of 500mm
• Structured with 3 rows of cross holes, Average front width of burner: 15mm, Hole diameter: 1.32mm, Distance between the center: 3.2mm.
• The test ladder used for cable installation is rigidly fitted to the support with a steel frame
• The vertically structured materials on both sides of the test ladder can be regulated to suit different cable sizes during test.
(Length: 1200mm, Height: 600mm, Gross weight: 18¡¾1kg)
• The shock wave generator of mild steel round rod, Diameter: 25¡¾1mm Length: 600¡¾5mm
• The shock wave generator is located 200¡¾5mm horizontally in one axis of the test ladder with a uneven distance of 400¡¾5mm with approx. 200mm
• Burner Position
• The front of burner is located at least 200mm above from the chamber¡¯s floor and at least 500mm separated from the chamber¡¯s sides.
• The horizontal axis of Burner is located 40~60mm downwards from the center cable sample and the vertical axis of burner is located approx. 100~120mm from vertical axis of cable sample.
• It has 2 type of mode which manual mode by control panel and auto mode by computer software.
  Before order, user can select it. It is customizing. And if order IEC 60331-11,12 and BS 6387, user can use one Slidacs system(various up to 1,000V power supplier). Cost should be down.
• Cable test description
• Manufacturer
• Voltage Test
• Cable Bending Radius
• Applied performance Requirements
• Test criterion or related standards
• Flame application time
• Voltage maintenance (ex. Fuse fails, interruption of circuit breaker)
• Rupture of conductor (ex. Lamp blackout)